2020 官网升级中!现在您访问官网的浏览器设备分辨率宽度低于1280px
请使用高分辨率宽度访问。

SHANGHAI XINGSHEN INSTRUMENT CO.,LTD.

Back to list

Normal type

The integrated ordinary temperature transmitter is a high-performance temperature transmitter with HART, which can be used in all industrial industries. It is compact and can be installed in thermal resistance, thermocouple, and junction box. The output and input are both effective galvanic isolation. The temperature transmitter converts the signal from the thermal resistance and thermocouple into a corresponding sensor characteristic, and outputs a two-wire 4~20mA current signal that has nothing to do with the load. The split type is to place the temperature transmitter in a flameproof enclosure installed on site. The product supports three-button operation. It adopts a fully isolated HART protocol intelligent module, which is convenient for on-site configuration. It has full isolation of input and output, and the transmitter has super strong anti-interference ability. The transmitter has a high-brightness white backlight meter, and the on-site temperature indication is eye-catching. Zero point and span adjustment do not affect each other, ultra-small temperature drift, and the performance reaches similar products in Europe and America. The transmitter can be integrated with thermocouples and thermal resistances, or can be installed separately. When installed separately, it can be easily fixed on vertical or horizontal pipes through optional mounting brackets.

Features
The transmitter can be integrated with thermocouples and thermal resistances, or can be installed separately. When installed separately, it can be easily fixed on vertical or horizontal pipes through optional mounting brackets.
Selection data Contact us
Technical Parameters

Input signal: thermocouple: S, B, E, K, R, J, T; thermal resistance: Pt100, Cu50
Output signal: 4~20mADC two-wire system, 4~20mA +HART
Maximum allowable error: thermocouple temperature transmitter ±0.5%FS; thermal resistance temperature transmitter ±0.2%FS
Power supply voltage: 24VDC (12~30V)
Load capacity: ≤650Ω (when powered by 24VDC)
Ambient temperature: -35℃~+75℃
Relative humidity: 5% to 95%
Nominal pressure: PN≤42.0MPa
Protection class: IP66
Electromagnetic interference: When there is a 20-1000MHz, 5W power radio transmitter working 0.5 meters away from the transmitter, the output variation error of the interference transmitter is less than ±0.15% of the range
Insulation resistance: ≥20MΩ
Flexibility: the radius of curvature of the deflection is not less than 5 times of its outer diameter
Electrical interface: 1/2NPT, M20×1.5
Explosion-proof mark: Ex d II B+H₂T1~T6 Gb , Ex ia II CT1~T6 Ga