2020 官网升级中!现在您访问官网的浏览器设备分辨率宽度低于1280px请使用高分辨率宽度访问。
Liquid level switch instrument performance
Repeatability: ±1% of set point
Operating range: 0.03~10 meters, resolution size 0.03 meters
Response time: 1~15 seconds, depending on the application
Stability: full range temperature compensation
Flow Switch Instrument Performance
Repeatability: ±1% of set point
Operating range: liquid, 0.003~1 m/s; gas, 0.03~160 m/s
Response time: 1~15 seconds, depending on the application
Stability: Drift less than 0.5%, full range temperature compensation
sensor
Thermal differential dual RTD probe
Fully welded sensor structure, 316L stainless steel or Hastelloy C alloy material; process connection: 3/4NPTM, DN25, other thread specifications or flange optional
Working temperature: standard -70~200℃, optional -70~300℃, -70~458℃;
Working pressure: vacuum to 3000PSIG (207BAR)
Cumulative radioactive dose: 252KGy
Anti-seismic Class I function appraisal
electronic unit
Input voltage: 220VAC, 50Hz, or 24VDC
Output relay: DPDT (double pole double throw), 5A, 250VAC
Ambient temperature: -40~70°C; one-piece or split installation (the split type uses low-smoke halogen-free flame-retardant cables, which are resistant to radiation)
Electrical interface: 1/2NPTF or M20×l.5F
shell
Stainless steel shell 304SS
Protection class IP66
Explosion-proof certification
CE certification